loading
×
500KW 416V/208V for Power Testing AC Resistive Load Bank

500KW 416V/208V for Power Testing AC Resistive Load Bank

500KW 416V/208V for Power Testing AC Resistive Load Bank

Precise regulation from 1kW to 500kW is achieved through a multi-stage switching combination (1kW to 200kW). Load element tolerance is ±2.5%, ensuring accurate test results.

● Dual-voltage compatible, multi-purpose in one unit: Supports 416Vac / 208Vac dual-voltage input, 50/60Hz universal, suitable for mainstream power distribution systems worldwide.

● Professional power configuration: Rated power 500kW (PF=1.0), resistive load, stable and high-precision testing.

● Fine stepping, flexible control: Supports fine stepping from 1kW with step combinations: 1/2/5/10/20/50/100/200kW, enabling accurate simulation of any load point.

● Strong heat dissipation & wide environmental adapt ability: High air volume 1600 CBM/Min forced horizontal air cooling, operating temperature -25℃ ~ +55℃, stable under extreme working conditions.

● Multiple safety protections: Equipped with thermal emergency cut-out, air flow switch, fan overload protection and emergency stop to fully ensure test safety.

If you have more questions, write to us
Just leave your email or phone number in the contact form so we can send you a free quote for our wide range of designs!
Customer service
detect