Project Overview
| Project Name | Indonesia — RATA 2000 kW Resistive Load Bank Project (RATA) | Client Name | Huawei |
| Project Site | Indonesia | Project Date | 2026.03 |
| Test Object | Generator testing | Test Purpose | Generator commissioning, performance verification, classification test |
| Supplied Equipment | 1 × RATA 2000 kW Resistive Load Bank, 415 Vac |
Customer Requirements
Project Background:
This project procures one set of RATA 2000 kW container-type resistive load banks, to be deployed at an outdoor test site in Indonesia. This operates at 415 Vac (also suitable for 400 V) with 3-phase 4-wire connection, 50 Hz / 60 Hz dual-frequency capability and unity power factor (1.0), providing fine 5 kW load step resolution for accurate loading of high-power generator sets. Loads are switched through AC contactors and connected via copper busbars. The containerized outdoor design (3,000 × 2,438 × 2,600 mm, about 6,000 kg per unit) is rated for −15 °C to +50 °C operation at altitudes up to 2,000 m, with standard ISO lifting points and forklift holes for easy handling.
Load Bank Technical Specification
Equipment Model: RATA 2000 kW Resistive Load Bank
|
Main Electrical Parameters |
|
| Load Type | Resistive Load Bank |
| Rated Capacity | 2,000 kW per unit |
| Power Factor | 1.0 |
| Test Voltage | 415 Vac (also suitable for 400 V); control voltage (auxiliary power supply): 400 Vac |
| Frequency | 50Hz / 60Hz |
| Phase | 3 Phase 4 Wire (3P4W) |
| Load Resolution | Load step resolution: 5 kW |
| Load Accuracy | Load element tolerance ≤ +2.5%; resistance error ± 3% |
| Cooling | Horizontal upwards forced-air cooling (side intake, top exhaust) |
| Load elements | Finned AISI304 stamped resistor elements with 8020 Ni-Cr alloy wire in stainless steel tubes filled with magnesium oxide powder; withstand temperature about 800 °C |
| Protection | Thermal emergency cut-out, air flow switch, fan overload protection, emergency stop, ground lead |
| Control system | System 1: local manual press-button control with electrical meter; System 2: PLC remote PC control with patented Nexus-1 software (RS485 / RJ45); System 3: 8-inch Windows three-proof industrial tablet PC (RT80) |
| Data functions | Real-time display of current, voltage, frequency, power and power factor; load data monitoring, acquisition, curves and charts; tables saved as Excel, curves saved as Word; English control software commissioned before delivery |
| Enclosure | Containerized cold-rolled stainless steel plate enclosure with painting (RAL 7035 or customizable); control chamber IP 54 outdoor |
| Dimensions (L × W × H) | 3000 × 2438 × 2600 mm (excluding 100–200 mm hinge/cover) |
| Estimated weight | About 6,000 kg per unit |
| Portability | Standard ISO lifting points and forklift holes |
| Duty cycle | Continuous |
| Insulation | Insulation impedance: DC 1000 V, 20 MΩ or above; insulation test voltage: 2000 Vac for 1 min |
| Load connections | Copper busbars (to connect with cables) |
| Load steps | Active load steps (kW): 5 kW × 2 + 10 kW × 2 + 20 kW + 50 kW + 100 kW × 2 + 200 kW + 500 kW × 3 |
| Tolerances | Voltage tolerance +5% (short-term operation); load element tolerance ≤ +2.5%; resistance error ± 3% |
| Ambient conditions | Operation −15 °C to +50 °C; altitude rating ≤ 2,000 m above sea level |
| Fans | 6 pcs airfoil axial fans; low-air-volume and high-temperature protection indication |
| Tablet controller | 8-inch Windows System three-proof handheld industrial tablet PC (RT80), Windows 10, N5100 + 8G + 128G |
| Documents provided | Factory report; operation & maintenance manual; structure diagrams & electrical schematic diagram after deposit |
| Main component brands | AC contactors for load switching; Contactors: Siemens / Schneider / ABB or equivalent; PLC: Siemens (remote I/O) |
| Warranty & support | 12-month warranty from receipt of goods; 7×24 technical support (subject to time zone difference); online meeting available anytime, free online technician guidance |
Marine Application Scenario
Scientific research, type test and factory acceptance of high-power diesel/gas generator sets; performance tests covering steady-state voltage and frequency regulation, transient load-on/load-off response, settling and fluctuation behavior;
full-load endurance and overload capability verification of marine main and auxiliary generator sets; load-step testing of propulsion converters, pumps and hotel loads at unity power factor; commissioning and periodic maintenance testing of the shipboard power station before sea trials.
Project Progress
Mar 03, 2026: RATA technical engineers and production personnel were present at the site, supporting equipment positioning, installation and commissioning.
Factory acceptance tests were completed before shipment, covering load step verification, protection function checks and full-load operation. On site, the two units were connected via copper busbars, control software was commissioned and configured before delivery,
and joint debugging with the customer's generator test platform was carried out. After the on-site handover tests, RATA provided operation training, complete technical documentation and continued 7×24 remote technical support.
Project Highlights
Standard containerized resistive load bank design with fine 5 kW load step resolution (5 kW × 2 + 10 kW × 2 + 20 kW + 50 kW + 100 kW × 2 + 200 kW + 500 kW × 3), enabling accurate loading from no-load to full load to truly restore actual power-consumption scenarios of generator sets;
Operates at 415 Vac (also suitable for 400 V), 3-phase 4-wire, with 50 Hz / 60 Hz dual-frequency capability. Two units can be operated in parallel for capacity expansion;
Three flexible control systems: local manual press-button control with electrical meter; remote PC control with the patented Nexus-1 software (RS485 / RJ45 communication, English control software commissioned before delivery); and an 8-inch Windows three-proof industrial tablet PC (RT80) for on-site control;
Real-time display and acquisition of current, voltage, frequency, power and power factor, with load data curves and charts; test tables are saved as Excel files and curves saved as Word documents for easy reporting;
Outdoor-container-type structure for easy maintenance. Equipped with comprehensive protections including thermal emergency cut-out, air flow switch, fan overload protection, emergency stop and ground lead;
Adaptable to harsh outdoor environments (operation −15 °C to +50 °C, altitude rating ≤ 2,000 m, control chamber IP 54 outdoor). Complete factory tests and on-site handover tests are performed, supported by comprehensive technical documentation, a 12-month quality warranty, and 7×24 after-sales service.