RATA UAE 1*2000kW Resistive Load Bank and 2*2800kw Generator Load Testing Resistive & Reactive Load Bank

Project Overview

Project Name UAE 1*2000kW Resistive Load Bank and 2*2800kw Generator Load Testing Resistive & Reactive Load Bank Project (RATA) Client Name  UAE
Project Site UAE Project Date 2026.09
Test Object Generator testing Test Purpose Generator commissioning, performance verification, classification test
Supplied Equipment 1 × RATA  2000 kW Resistive Load Bank + 2 × RATA  2800 kW / 3500 kVA Resistive-Reactive Load Bank, 415 Vac  

Customer Requirements

Project Background:

This project procures two sets of RATA container-type load banks — 1 × RATA  2000 kW Resistive Load Bank + 2 × RATA  2800 kW / 3500 kVA Resistive-Reactive Load Bank — to be deployed at an outdoor test site in Indonesia.

Both units operate at 415 Vac (also suitable for 400 V) with 50 Hz / 60 Hz dual-frequency capability: the resistive unit provides unity power factor (1.0) loading with fine 5 kW load step resolution through a 3-phase 4-wire connection, while the R-L unit provides 2,800 kW resistive and 2,100 kVar inductive capacity (3,500 kVA at 0.8 power factor,

adjustable between 0.8 and 1.0) with 10 kW / 10 kVar resolution through a 3-phase 3-wire connection.

The combination enables both pure resistive loading and realistic lagging power-factor simulation of actual loads. Loads are switched through AC contactors and connected via copper busbars.

The containerized outdoor designs (3,000 × 2,438 × 2,600 mm, about 6,000 kg for the resistive unit; 5,500 × 2,100 × 2,600 mm, about 15,000 kg for the R-L unit) are rated for −15 °C to +50 °C operation at altitudes up to 2,000 m, with standard ISO lifting points and forklift holes for easy handling.


Load Bank Technical Specification

Equipment Model: RATA 2000 kW Resistive Load Bank and RATA  2800 kW / 3500 kVA Resistive-Reactive Load Bank

Main Electrical Parameters

Load Type 2000kW: Resistive Load Bank; 2800kW: Resistive & Reactive (R-L) Load Bank
Rated Capacity 2000kW: 2,000 kW; 2800kW: 2,800 kW resistive + 2,100 kVar inductive (3,500 kVA @ 415 V)
Power Factor 2000kW: 1.0; 2800kW: 0.8–1.0 adjustable
Test Voltage 415 Vac (also suitable for 400 V); control voltage (auxiliary power supply): 400 Vac
Frequency 50Hz / 60Hz
Phase 2000kW: 3 Phase 4 Wire (3P4W); 2800kW: 3 Phase 3 Wire (3P3W)
Load Resolution 2000kW: 5 kW; 2800kW: 10 kW / 10 kVar
Load Accuracy Load element tolerance ≤ +2.5%; resistance error ± 3%
Cooling Horizontal upward forced-air cooling (side intake, top exhaust)
Load elements Resistive elements (both units): finned AISI304 stamped elements with 8020 Ni-Cr alloy wire in stainless steel tubes filled with magnesium oxide powder, withstand temperatures up to about 800 °C; 2800kW reactor: three-phase iron core reactor, oxygen-free enameled wire wound and sealed with paint, Baosteel high-quality cold-rolled oriented silicon steel sheets
Protection Thermal emergency cut-out, airflow switch, fan overload protection, emergency stop, ground lead
Control system System 1: local manual press-button control with electrical meter; System 2: PLC remote PC control with patented Nexus-1 software (RS485 / RJ45); System 3: 8-inch Windows three-proof industrial tablet PC (RT80)
Data functions Real-time display of current, voltage, frequency, power and power factor; load data monitoring, acquisition, curves and charts; tables saved as Excel, curves saved as Word; English control software commissioned before delivery
Enclosure Containerized cold-rolled stainless steel plate enclosure with painting (RAL 7035 or customizable); control chamber IP 54 outdoor
Dimensions (L × W × H) 2000kW: 3000 × 2438 × 2600 mm (excluding 100–200 mm hinge/cover); 2800kW: 5500 × 2100 × 2600 mm (excluding 100–200 mm hinge/cover)
Estimated weight 2000kW: about 6,000 kg; 2800kW: about 15,000 kg
Portability Standard ISO lifting points and forklift holes
Duty cycle Continuous
Insulation Insulation impedance: DC 1000 V, 20 MΩ or above; insulation test voltage: 2000 Vac for 1 min
Load connections Copper busbars (to connect with cables)
Load steps 2000kW: active load steps (kW) 5 kW × 2 + 10 kW × 2 + 20 kW + 50 kW + 100 kW × 2 + 200 kW + 500 kW × 3; 2400kW: active 10 kW + 20 kW × 2 + 50 kW + 100 kW + 200 kW × 3 + 500 kW × 4 (2,800 kW, 12 steps); reactive 10 kVar + 20 kVar × 2 + 50 kVar + 100 kVar × 2 + 150 kVar × 12 (2,100 kVar, 18 steps)
Tolerances Voltage tolerance +5% (short-term operation); load element tolerance ≤ +2.5%; resistance error ± 3%
Ambient conditions Operation −15 °C to +50 °C; altitude rating ≤ 2,000 m above sea level
Fans 2000kW: 6 pcs; 2400kW: 10 pcs — airfoil axial fans with low-air-volume and high-temperature protection indication
Tablet controller 8-inch Windows System three-proof handheld industrial tablet PC (RT80), Windows 10, N5100 + 8G + 128G
Documents provided Factory report; operation & maintenance manual; structure diagrams & electrical schematic diagram after deposit
Main component brands AC contactors for load switching; Contactors: Siemens / Schneider / ABB or equivalent; PLC: Siemens (remote I/O)
Warranty & support 12 months warranty from receipt of goods; 7×24 technical support (subject to time zone difference); online meeting available anytime, free online technician guidance

Application Scenario

Scientific research, type test and factory acceptance of high-power diesel/gas generator sets;

performance tests covering steady-state voltage and frequency regulation, transient load-on/load-off response, settling and fluctuation behavior;

full-load endurance and overload capability verification of main and standby generator sets;

pure resistive loading at unity power factor as well as lagging power-factor simulation (0.8–1.0 adjustable) of actual inductive consumers such as motors, transformers and cables;

commissioning and periodic maintenance testing of the power station.


Project Progress

Sep 03, 2026: RATA technical engineers and production personnel were on site, supporting equipment positioning, installation, and commissioning.

Factory acceptance tests were completed before shipment, covering load step verification, protection function checks and full-load operation.

On site, the two units were connected via copper busbars, control software was commissioned and configured before delivery,

and joint debugging with the customer's generator test platform was carried out. After the on-site handover tests, RATA provided operation training, complete technical documentation and continued 7×24 remote technical support.


4 (59)
1 (135)
2 (109)

Project Highlights

Two complementary containerized load banks: the 2000kW resistive unit with fine 5 kW load step resolution (5 kW × 2 + 10 kW × 2 + 20 kW + 50 kW + 100 kW × 2 + 200 kW + 500 kW × 3) and the 2800kW R-L unit with 10 kW / 10 kVar resolution (12 resistive steps totaling 2,800 kW;

18 reactive steps totaling 2,100 kVar), enabling accurate loading from no-load to full load;

Both units operate at 415 Vac (also suitable for 400 V) with 50 Hz / 60 Hz dual-frequency capability. The R-L unit provides adjustable power factor from 0.8 to 1.0 for realistic lagging load simulation of motors, transformers and other inductive equipment;

Three flexible control systems: local manual press-button control with electrical meter;

remote PC control with the patented Nexus-1 software (RS485 / RJ45 communication, English control software commissioned before delivery);

and an 8-inch Windows three-proof industrial tablet PC (RT80) for on-site control;

Real-time display and acquisition of current, voltage, frequency, power and power factor, with load data curves and charts; test tables are saved as Excel files and curves saved as Word documents for easy reporting;

Outdoor-container-type structure for easy maintenance. Equipped with comprehensive protections, including thermal emergency cut-out, airflow switch, fan overload protection, emergency stop and ground lead;


Adaptable to harsh outdoor environments (operation −15 °C to +50 °C, altitude rating ≤ 2,000 m, control chamber IP 54 outdoor). We perform complete factory tests and on-site handover tests, supported by comprehensive technical documentation, a 12-month quality warranty, and 7×24 after-sales service.


2000kw Resistive Load Bank  Product photos

图片6
44
33
22 (2)

2800kW 3500kvar Resistive & Reactive Load Bank Product photos

2222
111
333
222
prev
RATA 2000kW Generator Load Testing Resistive Load Bank
recommended for you
Get in touch with us

Deyang Rata Technology Co., Ltd.

Contacts: Gong Zhenhua
Phone/ WhatsApp: 0086-13890270038
Address: Hongyu Road East, Jinshan Industrial Park, Luojiang Disctrict, Deyang. China

Shenzhen Rata Technology Co., Ltd.

Tel: 0086-15196362093
Address: Room 102, Building 3, Huahan Science & Technology Industrial Park, No.16 West Jinniu Road, Heping Community, Pingshan Subdistrict, Pingshan District, Shenzhen, Guangdong Province, 518122, P.R.China
Customer service