Product Introduction
Built for reliability in demanding environments, it features forced-air cooling, thermal protection, and an IP23-rated enclosure, operating steadily from -15°C to +50°C. With quick connectors, safety cut-offs, and integrated casters, it delivers safe, portable, and repeatable testing for R&D, production, and quality validation.
Estimated cabinet enclosure (mm)
This info given is our standard load bank features. we are constantly looking to improve our design. We reserve the right to change with prior notice. The finished design might slightly vary from this given TDS.
Main Parameters
| Model No. | RTDCS14L |
| Country of origin | China |
| Rated Testing Voltage | 48V DC |
| Rated Current | 300A |
| Load step resolution | 1A |
| Estimated Width(mm)*Depth(mm)*Height(mm) | 300*550*600mm |
| Estimated weight | 65kg |
| Other information | |
| Load Connections | Quick connectors |
| Protection | Thermal emergency cut out |
| Fan switch | |
| Fan overload protection | |
| Emergency stop | |
| Airflow direction | Horizontal air forced cooling |
| Fan type | Airfoil axial fan |
| Load switching contactor type | DC contactors |
| Rated minimum / maximum ambient temp. operation | -15°C to +50°C |
| Altitude rating | ≤2000 [m.a.s.l] |
| Control chamber IP rating | IP 23 Indoor |
| Enclosure material | Cold rolled stainless steel plate with painting. |
| Enclosure color | RAL 7035 |
| Resistor material | finned resistor, AISI304/stamped elements |
| 8020Ni-Cr alloy | |
| Resistance error | 1.5%~±3% |
| Portability | Casters, lifting rings |
| Load bank control system | |
| Manual control + PC remote | Press buttons or touch screen + PLC remote |