RATA 300VDC 400A DC Load Bank is a high-precision, air-cooled resistive load testing unit designed for DC power systems of next-generation data centers, battery energy storage systems (BESS), UPS rectifiers, chargers and other DC power validation applications.
5.0
Warranty time:
2 years
Delivery time:
6 weeks
ISO Certification:
ISO9001/ISO14001
Brand:
RATA
Factory Price:
Negotiate
Supply Ability:
200,000 Piece/Pieces per Month
Port:
Shanghai and Guangzhou are both available
Payment Terms:
L/C,Cash,Western Union,T/T, Paypal
Min.Order Quantity:
1 pcs
ODM & OEM:
Available
Certification:
CE 60204 Standard​
design customization

    oops...!

    no product data.

    Go to homepage
    Rata-300VDC 400A
    Rata-300VDC 400A

    Product Introduction

    The RATA 300VDC 400A DC Load Bank is a new air-cooled resistive load testing unit rated at 300Vdc / 400A. It is specially designed for acceptance testing and performance verification of DC power systems, including data center server power supplies, BESS battery clusters, UPS rectifiers, chargers and DC power sources.


    With a load resolution of 1A and a whole-machine accuracy of ±3%, the unit provides precise and stable load simulation. It adopts a horizontal airflow design with 12 industrial-grade fans (380 CFM per fan), delivering reliable heat dissipation within a compact footprint of 600×1250×900mm and an estimated weight of 130kg. 200A DC quick connectors allow fast and safe on-site installation.


    Control is provided by an HMI touch screen locally and PC software remotely via RJ45 / Modbus TCP, supporting real-time monitoring of voltage, current, power and load status. It is applicable to load testing of data center DC power systems, BESS, UPS systems, generator testing and power grid balancing.

    5 (31)

    Key Features and Advantages

    IMG_6589 拷贝 2
    High-accuracy DC load testing
    1A load resolution and ±3% whole-machine accuracy.
    300VDC 400A DC Load Bank(Air Cooling)For Data Center & BESS Testing 8
    Horizontal airflow layout
    Horizontal airflow design with 12 industrial fans (380 CFM per fan) for flexible installation.
    调节
    Industrial resistive elements
    Industrial-grade resistive elements with ±2.5% component tolerance compatibility for maximum utilization.
    company (5)
    Smart control system
    HMI touch screen locally, PC software remotely via Modbus TCP (RJ45).
    300VDC 400A DC Load Bank(Air Cooling)For Data Center & BESS Testing 11
    Comprehensive safety protection
    Fans overload, thermal emergency cut-out and emergency stop.
    IMG_6594 拷贝
    Robust and customizable design
    IP23 enclosure, universal wheels and lifting lugs.
    IMG_6591 拷贝
    Rapid field setup
    Fast on-site installation with 200A DC quick connectors and a compact 600×1250×900mm footprint.
    300VDC 400A DC Load Bank(Air Cooling)For Data Center & BESS Testing 14
    Wide applications
    Data center DC power, BESS, UPS, genset testing and power grid balancing.

    Engineering Drawing (only for Ref.)

    1 (133)
    1 (133)

    Product Specifications

    Electrical parameter
    Rated voltage. 300Vdc
    Rated Current 400A
    Wires DC300V DC+ / DC-
    Load resolution 1A
    Voltage Tolerance (Short Term Operation) +5%
    Load component tolerance ± 2.5%
    Whole machine accuracy ± 3%
    Load connection Quick connectors
    (200A)
    Control power External
    Control voltage 230Vac 1p 60Hz
    Enclosure structure
    Canopy/ container Canopy
    Size(Width*Depth*Height mm) 600*1250*900mm
    Air direction Horizontal
    Quantity of fans 12
    Air volume(CFM/Fan) 380
    Portability Universal wheels&
    lifting lugs
    IP grade of control chamber IP 23
    IP grade of complete enclosure IP 23
    Estimated weight(kg) 130kg
    Protections
    Fans overload
    Thermal emergency cut out
    Fan switch
    Emergency stop
    Load bank control
    Temperature -25 °C to +55°C
    Latitude ≤ 2000 m.a.s.l
    Load switching DC contactor
    Digital meter V/A/kW/Hz/Pf.
    Interface RJ45
    Type of communication Modbus TCP
    Local control HMI touch screen
    Remote control PC software

    Key details

    IMG_0660 拷贝
    IMG_0660 拷贝
    IMG_0661 拷贝
    IMG_0661 拷贝
    IMG_0662 拷贝
    IMG_0662 拷贝
    IMG_0677 拷贝
    IMG_0677 拷贝
    IMG_3025 拷贝
    IMG_3025 拷贝
    IMG_3103 拷贝
    IMG_3103 拷贝

    FAQ

    1
    Why do data center and BESS testing require DC load banks?
    With rising power consumption of AI servers and the adoption of high-voltage DC (HVDC) power architectures, DC equipment such as energy storage systems, server power supplies and charging modules requires real thermal loads to verify its power capability. A DC load bank precisely simulates the DC-side load current to verify full-load capacity, voltage regulation accuracy and operational reliability of the power system.
    2
    How does the 300VDC 400A load bank achieve heat dissipation?
    The unit adopts a horizontal airflow design with 12 industrial-grade fans (380 CFM each) for forced air cooling. Heat generated by the resistive elements is discharged directly out of the enclosure, delivering strong cooling capacity with a simple structure and easy maintenance.
    3
    What control methods are supported?
    Local control via an HMI touch screen and remote control via PC software are supported. Communication is Modbus TCP over RJ45, providing real-time monitoring of voltage, current, power and load status, and easy integration with data center monitoring systems.
    4
    What data center equipment can this product test?
    Main applicable equipment includes server power supplies, BESS battery clusters, UPS rectifiers, charging modules/chargers and DC generators.
    5
    Why is thermal load testing of servers necessary?
    Electrical energy consumed by running servers is ultimately converted into heat energy. By simulating a real 400A DC IT load, this load bank verifies power supply capability, cooling capacity, temperature control stability and overall reliability of the computer room environment.
    6
    What is the function of Modbus TCP?
    Modbus TCP enables remote load regulation, data acquisition and real-time status monitoring, allowing seamless integration with BMS or DCIM systems.
    7
    Is on-site installation and movement convenient?
    Yes. The unit weighs about 130kg and comes with universal wheels and lifting lugs. The load connection uses 200A DC quick connectors, and the compact 600×1250×900mm footprint allows flexible deployment in machine rooms and test sites.
    8
    Do you provide installation and testing support?
    Yes, Rata provides on-site testing services, including equipment installation, configuration, and data logging.
    9
    Typical product delivery time?
    6 weeks.
    10
    Warranty service?
    2 years.
    11
    How many countries have you exported to?
    We export to over 80 countries worldwide.
    12
    Why choose us?
    We have ISO、CE certification and are Authorized factories for Siemens and Schneider Electric brands.
    Get in touch with us
    just leave your email or phone number in the contact form so we can send you a free quote for our wide range of designs
    Related Products

    Deyang Rata Technology Co., Ltd.

    Contacts: Gong Zhenhua
    Phone/ WhatsApp: 0086-13890270038
    Address: Hongyu Road East, Jinshan Industrial Park, Luojiang Disctrict, Deyang. China

    Shenzhen Rata Technology Co., Ltd.

    Tel: 0086-15196362093
    Address: Room 102, Building 3, Huahan Science & Technology Industrial Park, No.16 West Jinniu Road, Heping Community, Pingshan Subdistrict, Pingshan District, Shenzhen, Guangdong Province, 518122, P.R.China
    Customer service