Load bank application for an oil drilling platform include simulate actual load conditions, monitoring and adjusting the output power, voltage, current, frequency, and other parameters of the generator set in real time, to ensure the stability and reliability of the generator set under various working conditions.
Applications:
Generator testing & commissioning
Data center UPS / PDU testing
Renewable energy (solar / wind / BESS)
Industrial power systems
product introduction
Common Contents of Load Testing for Oil Drilling Platforms,This product caters the diverse needs of the customers.
(1) Power test: Verify whether the generator set can output the specified power under different load levels, including full power, partial power, and other different working conditions.
(2) Voltage stability test: Check the fluctuation of the output voltage during loading and unloading processes to ensure that the voltage remains within the allowable range.
(3)Frequency stability test: Monitor the stability of frequency during load changes to ensure the quality of power supply.
(4) Overload capacity test: Determine the ability and duration of the generator set to withstand a certain proportion of normal loads.
product specification
Model No. | S2000L |
Country of origin | China |
Rated testing voltage | 690Vac |
Control voltage(Auxiliary power supply) | 690Vac |
Frequency | 50HZ |
power(kW PF=1) | 2000kW |
Load step resolution | 10kW |
Load step(kW) | 10KW+20K W+20K W+50K W +100KW+200K W+200KW+ 400KW+500KW+500KW |
Phases | 3 |
Wires(Delta connection) | 3 |
Voltage Tolerance (Short Term Operation) | +5% |
Load Element Tolerance | ≤+2.5% |
Insulation Test | 1500 Vac |
Load Connections | zine coated Copper busbars |
Protection | Thermal emergency cut out |
Air flow switch | |
Fan overload protection | |
Emergency stop | |
Airflow volume(Approx. CMM) | 2200 CM/Min. |
Airtlow direction | horizontal upwards air forced cooling |
Fans Nos.(tan motors power) | 6 pcs . (3kw each) |
Load switching contactor type | AC contactors |
Rated maximum ambient temp. operation | +50°C /+122°F |
Rated minimum ambient temp. operation | -20°C / -4°F |
Altitude rating | <500⌊m.a.s.1⌊ or customized |
Enclosure material | IP 54 outdoor |
Portability | Standard ISO lifting points |
Enclosure dimensions(roughly) | |
Length(mm) | 4500 |
Width(mm) | 2438 |
Height(mm) | 2600 |
Weight of load bank with wind-shields (KG) | 8.000 Maximum |
Load bank control system | |
Manual control | Local toggle buttons or push buttons |
PLC control +handhold controller | Remote PC control with patented software Nexus-1 |