loading

Detailed Parameter Table Of Rata R1000kW/10.5kV Medium Voltage Load Bank System

Deyang Rata Technology Co., Ltd.

1000kW/10.5kV medium voltage load bank system parameters

System composition

Outdoor container type, resistive load, data acquisition, electrical control part, cooling device and load protection control

Rated Capacity

R1000kW

Test voltage

AC 400V ; AC 10kV (meet the 10kV test through the transformer )  

Rated frequency

50Hz

Test frequency

50Hz

Load characteristics

Resistive load, to meet multiple parallel work

Power Factor

1.0

Load connection

Copper bar ;

input port during high voltage test ;

independent input port for low voltage test

Loading accuracy

± %

Three-phase balance

Unbalance is less than or equal to 3%

Way of working

Continuously working

Working power

Single AC380V/50Hz/three-phase four-wire system/bottom in and bottom out/40kW

Cooling method

Forced air cooling (side inlet and top outlet)

Insulation class

F

Parameter measurement accuracy

The sampling accuracy of the instrument is 0.2 grade; (voltage ±0.5%, current ±0.5%, frequency ±0.5%

0.1%, power ±1%, power factor ±1%)

Minimum load resolution

Rate

1kW

Resistive load capacity

1000kW

Resistive Load Binning

Resistive Loads ( R):

1KW、2KW*2、5KW、10KW*2、20KW、50KW、100KW*9

Resistance tube

For each resistance element : Insulation resistance DC1000V 20M Ω or more Withstand voltage  

AC2000V 1 minute resistance error of each resistance tube: ±3%

Resistive material

Special alloy resistors

Hot and cold state changes

≤2%

Load protection

Short circuit, over voltage, over current, high temperature, air volume, emergency shutdown protection

Atmospheric pressure

86-106Kpa

Dimensions

60 00mm×2438mm×2 500mm (L×W×H; for reference only)

Weight

About 18000Kg (for reference only)

Protection class

IP56 when not in use ; IP20 in load area when in use

Use location

Outdoor

Working status

Continuously working

Installation and transportation

The box has load-bearing lifting holes, which meet the conditions of long-distance transportation by automobiles.

Load expansion

Parallel expansion of 1+N load containers

Color

According to customer requirements

Scope of application

Suitable for gas generator sets, marine diesel generator sets, land diesel generators

Group, UPS system

System standard

Meet the test of international standard, ship standard, military standard and telecommunication standard

 

Remote console parameters

System composition

Laptop (host computer software)

Communication Interface

Network port, connect the load through network cable fiber

data collection

Directly access the sampling data from the output of the generator set, and use the MOXA server to transmit the data

Working power

AC220V\50Hz

control function

Staged loading can be set on the software, and staged loading can be performed automatically.

Manual loading: input power and power factor, that is, loading according to the specified value.

Preset loading: Enter the relevant parameters of the generator set, you can select preset ratios such as 0%, 25%, 50%, 75%, 100% to 110%, and automatically calculate the corresponding power to achieve fast loading.

Automatic loading: The power and duration of multiple loading stages can be set during testing, and stage testing can be performed automatically. Pause at any time during loading, or skip to the next stage

Test function

Basic parameter detection: It can detect the steady-state three-phase voltage, current, active power, reactive power, apparent power, power factor, active energy, reactive energy, frequency and other parameters of the generator set.

Dynamic test: with generator set fluctuation test, sudden addition unloading test, setting test, etc., can automatically test the maximum and minimum values of voltage, current, frequency, and recovery time for sudden load changes

Data collection interval

The minimum resolution time of steady state data is 1s , and the minimum resolution time of transient data is 40μs

Graphical display

lSupport display and print real-time voltage, current, power, frequency, power factor , generator oil pressure, water temperature curve

lSupport display and printing of transient curves ( sudden voltage, current, frequency,

sudden discharge voltage, current, frequency)

lSupport display and printing of harmonic curves ( harmonic voltage curve and histogram, harmonic current curve and histogram )

lSupport to display the recording curve graph

 The above is the R1000kW/10.5kV medium voltage load bank system parameter table of Deyang Rata Technology Co., Ltd. For more information, please refer to the products on this site: 1000kW Load Bank.

prev.
Introdução do Banco de Carga de Média Tensão Rata R1000kW Inteligente Personalizado
Qual é o conteúdo do teste de aluguel de banco de carga de 1 MW? Quais são os controles?
Próximo
recomendado para você
sem dados
Entre em contato conosco
Customer service
detect