Deyang Rata Technology Co., Ltd. 1000kW/10.5kV medium voltage load bank system parameters | |
System composition | Outdoor container type, resistive load, data acquisition, electrical control part, cooling device and load protection control |
Rated Capacity | R1000kW |
Test voltage | AC 400V ; AC 10kV (meet the 10kV test through the transformer ) |
Rated frequency | 50Hz |
Test frequency | 50Hz |
Load characteristics | Resistive load, to meet multiple parallel work |
Power Factor | 1.0 |
Load connection | Copper bar ; 1 input port during high voltage test ; 1 independent input port for low voltage test |
Loading accuracy | ± 3 % |
Three-phase balance | Unbalance is less than or equal to 3% |
Way of working | Continuously working |
Working power | Single AC380V/50Hz/three-phase four-wire system/bottom in and bottom out/40kW |
Cooling method | Forced air cooling (side inlet and top outlet) |
Insulation class | F |
Parameter measurement accuracy | The sampling accuracy of the instrument is 0.2 grade; (voltage ±0.5%, current ±0.5%, frequency ±0.5% 0.1%, power ±1%, power factor ±1%) |
Minimum load resolution Rate | 1kW |
Resistive load capacity | 1000kW |
Resistive Load Binning | Resistive Loads ( R): 1KW、2KW*2、5KW、10KW*2、20KW、50KW、100KW*9 |
Resistance tube | For each resistance element : Insulation resistance DC1000V 20M Ω or more Withstand voltage AC2000V 1 minute resistance error of each resistance tube: ±3% |
Resistive material | Special alloy resistors |
Hot and cold state changes | ≤2% |
Load protection | Short circuit, over voltage, over current, high temperature, air volume, emergency shutdown protection |
Atmospheric pressure | 86-106Kpa |
Dimensions | 60 00mm×2438mm×2 500mm (L×W×H; for reference only) |
Weight | About 18000Kg (for reference only) |
Protection class | IP56 when not in use ; IP20 in load area when in use |
Use location | Outdoor |
Working status | Continuously working |
Installation and transportation | The box has load-bearing lifting holes, which meet the conditions of long-distance transportation by automobiles. |
Load expansion | Parallel expansion of 1+N load containers |
Color | According to customer requirements |
Scope of application | Suitable for gas generator sets, marine diesel generator sets, land diesel generators Group, UPS system |
System standard | Meet the test of international standard, ship standard, military standard and telecommunication standard |
Remote console parameters | |
System composition | Laptop (host computer software) |
Communication Interface | Network port, connect the load through network cable \ fiber |
data collection | Directly access the sampling data from the output of the generator set, and use the MOXA server to transmit the data |
Working power | AC220V\50Hz |
control function | Staged loading can be set on the software, and staged loading can be performed automatically. Manual loading: input power and power factor, that is, loading according to the specified value. Preset loading: Enter the relevant parameters of the generator set, you can select preset ratios such as 0%, 25%, 50%, 75%, 100% to 110%, and automatically calculate the corresponding power to achieve fast loading. Automatic loading: The power and duration of multiple loading stages can be set during testing, and stage testing can be performed automatically. Pause at any time during loading, or skip to the next stage |
Test function | Basic parameter detection: It can detect the steady-state three-phase voltage, current, active power, reactive power, apparent power, power factor, active energy, reactive energy, frequency and other parameters of the generator set. Dynamic test: with generator set fluctuation test, sudden addition / unloading test, setting test, etc., can automatically test the maximum and minimum values of voltage, current, frequency, and recovery time for sudden load changes |
Data collection interval | The minimum resolution time of steady state data is 1s , and the minimum resolution time of transient data is 40μs |
Graphical display | lSupport display and print real-time voltage, current, power, frequency, power factor , generator oil pressure, water temperature curve lSupport display and printing of transient curves ( sudden voltage, current, frequency, sudden discharge voltage, current, frequency) |
lSupport display and printing of harmonic curves ( harmonic voltage curve and histogram, harmonic current curve and histogram ) lSupport to display the recording curve graph |
The above is the R1000kW/10.5kV medium voltage load bank system parameter table of Deyang Rata Technology Co., Ltd. For more information, please refer to the products on this site: 1000kW Load Bank.