Product Overview
- Rata container-type resistive load bank, model 2000 kW (2 MW) rated at 6000 VAC, 3-phase, designed primarily for outdoor use (IP54).
- Purpose-built for generator load testing (notably oilfield generators) and can be operated locally or remotely via PC using Modbus TCP / RJ45 (RS485/RS232 optional).
- Rugged, transportable unit with hoisting lugs, dimensions 4500 × 2530 × 2600 mm and weight ~6,500 kg.
Product Features
- Resistive-only 2 MW capacity with stepped configuration: 50kW+50kW+100kW+100kW+200kW+500kW+500kW+500kW.
- 8020 Ni‑Cr alloy finned resistors and forced-air cooling (horizontal intake, vertical ducted exhaust).
- Protection suite: high-temperature alarm, low air-volume alarm, fan interlock, phase sequence, overvoltage/overcurrent, short circuit, smoke alarm, temp & humidity control, access control, emergency stop.
- Control: local panel switching + Siemens PLC remote control; digital metering for V, A, kW, power factor and frequency; data save/printing and multilingual UI.
- Customizable (OEM/ODM) finishes, logos, color, and communication interfaces.
Product Value
- Enables safe, repeatable, full-load testing and commissioning of large generators and power systems, reducing operational risk.
- Shortens commissioning and maintenance cycles and provides accurate load data for performance verification.
- Durable outdoor design and comprehensive protections minimize downtime and extend service life in harsh environments.
- Global support and testing services (Factory Acceptance Test, onsite training) improve deployment speed and operator confidence.
Product Advantages
- High tolerance and robust design tailored for heavy-duty, outdoor applications (IP54 containerized solution).
- Modular load steps for flexible, precise loading profiles up to 2 MW.
- Strong after-sales (7×24 support), global delivery network, and partnerships with major suppliers (ABB, Schneider, Siemens, etc.).
- Customization options and communication flexibility (Modbus TCP, RS485, RS232) for easy integration into customer systems.
- Proven manufacturing and quality control with FAT, export packaging, and operator training available.
Application Scenarios
- Load testing and commissioning of oilfield and industrial generators.
- Routine maintenance, overload and capacity testing for power plants, utilities, and large industrial sites.
- Factory acceptance testing for gensets and electrical equipment manufacturers.
- Backup power verification for data centers, hospitals, and critical infrastructure.
- Rental fleet for construction sites, EPC projects, and temporary power system validation.
|
Product name |
2000kW resistive load bank; |
| Model number | RT2000kWLB; |
| Design | Container type with air duct for outdoor use; |
|
Rated power |
AC6kV. Connected with tin plated copper bar. |
| Control power |
AC380V,3 phase 4 wire,connected with terminal; |
| Frequency | 50Hz/60Hz; |
| Loading accuracy | ≤ 3%; |
| 3 phase balance | Unbalance degree ≤ 3%; |
| Duty cycle | Continuous work |
| Insulation | F |
|
Operation mode |
Local panel switching control +remote PC control,Siemens PLC system,RJ45 communication interface,load data save and pringting,operation software language can be user's local language |
|
Load steps |
50kW resolution.50kW+50kW+100kW+100kW+200kW+500kW+500kW+500kW |
|
Resistor |
8020 Ni-Cr alloy finned resistor; |
|
Cooling system |
Forced air cooling;horizontal air intake and vertical outlet with air duct;Axial fan,noise less than 80dB at 3m distance; |
| Enclosure | Q235 steel,powder coated. |
|
Protection |
High temperature,low air volume,phase sequence,short circuit,fan interlock,access control,smoke alarm,temperature and humidity control,emergency stop; |
|
Digital meter |
Voltage,current,power,power factor and frequency; |
|
Load expansion |
Parallel expansion of multiple loads; |
|
Standard |
Meet international standard,ship standard,military standard and telecommunication standard |
|
Movement |
Hoisting,4 lift lugas on the top the local bank enclosure |
|
Color |
Customized color |
| Dimensions | 4500mm*2530mm*2600mm (L*W*H) |
| Weight | 6500Kg |
|
Ambient temperature |
-20℃ to 50℃ |
|
Humidity |
Up to 100% |
|
Altitude |
Up to 2500m |
|
Atmospheric pressure |
86 to 106kPa |
| Warranty period | 12 months start from commissioning at clients' ste |
| Packing | Wrapping film |