Product Overview
- Rata container-type resistive dummy load bank rated at 2000 kW (2 MW) for 3-phase systems, designed for outdoor use (IP54) with rated voltage 6000 VAC.
- Built for oil-field generator load testing and other large-scale power-testing needs; enclosure size ~4500×2530×2600 mm and weight ~6500 kg.
- Robust construction with hoisting lugs, horizontal air intake and vertical hot-air outlet, and export-ready packing.
Product Features
- Resistive-only design using 8020 Ni-Cr alloy finned resistors and forced-air cooling.
- Modular load steps: 50+50+100+100+200+500+500+500 kW for flexible loading.
- Control via local panel switching and remote PC (Siemens PLC, operation software, data save/print), communication by Modbus TCP over RJ45 (RS485/RS232 optional).
- Digital metering for voltage, current, power, power factor and frequency.
- Comprehensive protections: high-temperature alarm, low-air-volume alarm, fan interlock, phase sequence, over-voltage/current, short circuit, smoke alarm, temperature & humidity control, access control, and emergency stop.
Product Value
- Enables safe, accurate and repeatable load testing of large generators and power systems to verify performance, endurance and commissioning.
- Reduces downtime and risk by simulating real-load conditions and capturing test data (logging/printing/local-language software).
- Customizable (OEM/ODM, logo, color) to fit integration and branding needs; packaged and shipped worldwide with factory acceptance test and operator training options.
Product Advantages
- High tolerance and market reputation backed by Deyang Rata Technology’s quality production management and efficiency.
- Strong global support: 27-city presence, 50 delivery centers, 7×24 delivery capacity, and 7×24-hour after-sales service with quick response.
- Trusted ecosystem: partnerships with ABB, Schneider, Omron, Siemens, Phoenix Contact, Delixi.
- Value-added services: factory acceptance testing, free on-site operator training during visits, and flexible communication/interface options.
Application Scenarios
- Oil-field and standby diesel generator load testing and commissioning.
- Power plant and substation maintenance, load bank testing during repairs or upgrades.
- Factory acceptance testing of large electrical equipment, UPS and backup systems validation.
- Research and development labs, industrial facilities, and any scenario requiring controlled dissipation of electrical power for performance and safety verification.
|
Product name |
2000kW resistive load bank; |
| Model number | RT2000kWLB; |
| Design | Container type with air duct for outdoor use; |
|
Rated power |
AC6kV. Connected with tin plated copper bar. |
| Control power |
AC380V,3 phase 4 wire,connected with terminal; |
| Frequency | 50Hz/60Hz; |
| Loading accuracy | ≤ 3%; |
| 3 phase balance | Unbalance degree ≤ 3%; |
| Duty cycle | Continuous work |
| Insulation | F |
|
Operation mode |
Local panel switching control +remote PC control,Siemens PLC system,RJ45 communication interface,load data save and pringting,operation software language can be user's local language |
|
Load steps |
50kW resolution.50kW+50kW+100kW+100kW+200kW+500kW+500kW+500kW |
|
Resistor |
8020 Ni-Cr alloy finned resistor; |
|
Cooling system |
Forced air cooling;horizontal air intake and vertical outlet with air duct;Axial fan,noise less than 80dB at 3m distance; |
| Enclosure | Q235 steel,powder coated. |
|
Protection |
High temperature,low air volume,phase sequence,short circuit,fan interlock,access control,smoke alarm,temperature and humidity control,emergency stop; |
|
Digital meter |
Voltage,current,power,power factor and frequency; |
|
Load expansion |
Parallel expansion of multiple loads; |
|
Standard |
Meet international standard,ship standard,military standard and telecommunication standard |
|
Movement |
Hoisting,4 lift lugas on the top the local bank enclosure |
|
Color |
Customized color |
| Dimensions | 4500mm*2530mm*2600mm (L*W*H) |
| Weight | 6500Kg |
|
Ambient temperature |
-20℃ to 50℃ |
|
Humidity |
Up to 100% |
|
Altitude |
Up to 2500m |
|
Atmospheric pressure |
86 to 106kPa |
| Warranty period | 12 months start from commissioning at clients' ste |
| Packing | Wrapping film |