Product Overview
1) Product overview
Product Features
- 600 kW AC resistive load bank (specification example: R600kW/400VAC/50Hz/PF1.0) designed for performance testing and aging of high‑power UPS, inverters, switching power supplies and diesel generator sets.
Product Value
- Modular, single‑container formation including dry resistance elements, electrical control components and measurement/control system.
Product Advantages
- Continuous operation capability with forced‑air cooling and options for side or top air outlet.
Application Scenarios
2) Product features
- Dry resistance elements with high insulation and withstand voltage (insulation DC1000V/100MΩ+, AC 2000V/5min).
- High power density, no “red‑heat” phenomenon, automatic overheat protection and protection against fan failure.
- Load control: local manual, local automatic or remote automatic; minimum step 1 kW; loading accuracy ≤3%; three‑phase unbalance ≤3%.
- Measurement/display of three‑phase voltage, currents, frequency, power; display accuracy 0.5, sampling accuracy 0.2.
- Expandable by parallel connection of multiple load containers; transport features (lifting holes, optional rollers); customizable color and parameters.
3) Product value
- Provides scientific, repeatable and reliable means to validate and commission high‑power AC power equipment, reducing field failures and downtime.
- Enables full performance, endurance and safety verification for manufacturers, service providers and end users.
- Customizable and modular design shortens installation, maintenance and upgrade cycles and improves lifecycle management of power systems.
4) Product advantages
- Independently developed power consumption components and modular architecture for easier maintenance and high reliability.
- Robust safety suite: short‑circuit, overcurrent, overtemperature and fan‑fault protections plus automatic overheating protection to prevent element burning.
- High measurement accuracy and fine load step resolution offering precise, reproducible test conditions.
- Compliance capability with international, marine, military and telecommunication standards; on‑site and factory acceptance testing and supplier training support.
5) Application scenarios
- Commissioning, routine testing and aging of UPS systems, inverters, switching power supplies and diesel generator sets.
- Manufacturing test benches for power equipment and quality control labs.
- Data centers, telecommunication sites, power stations and military or shipboard power testing where standards compliance and reliable load simulation are required.
- Field service, maintenance contractors and rental/test houses performing site acceptance testing and on‑site diagnostic verification.
|
Note: all parameters are for reference only and can be customized |
|
|
Product name |
600kW load bank |
|
Specifications |
R600kW/400VAC/50Hz/PF1.0 |
|
Formation |
One load bank(Including dry resistance load, electrical control components, measurement and control system) |
|
Load step |
According to customer needs |
|
Load connection |
Copper bar |
|
Resistor |
Each resistance element: insulation impedance DC1000V/100MΩ above Withstand voltage ac 2000V for 5min Resistance error of each resistance tube:±3% |
|
Load control |
Local manual control, local automatic control or remote automatic control can be selected |
|
Loading accuracy |
Less than or equal to 3% |
|
Three phase balance |
Unbalance degree less than or equal to 3% |
|
Minimum step |
1kW |
|
Working mode |
Continuous work |
|
Load protection |
Short circuit, overcurrent, high temperature, fan fault protection |
|
External power |
TN-C,380V/50Hz |
|
Cooling mode |
Forced air cooling, side air outlet or top air outlet |
|
Insulation class |
F |
|
Measurement accuracy |
The display accuracy is 0.5,the sampling accuracy is 0.2 |
|
Electrical parameter display |
Three phase voltage, three-phase current, frequency, power, etc |
|
Load expansion |
Parallel expansion of multiple load containers |
|
Standard |
Meet international standard, ship standard, military standard and telecommunication standard |
|
Transport |
The load bank is equipped with load-bearing lifting holes, and the bottom can be equipped with rollers to meet the requirements of long-distance transportation |
|
Color |
Customized |
|
Ambient temperature |
-20℃ to 50℃ |
|
Humidity |
Up to 100% |
|
Altitude |
Up to 2500m |
|
Atmospheric pressure |
86 to 106kPa |