Product Introduction
RATA's 7500kVA Resistive and Reactive Mobile Load Bank System is a high-power testing solution engineered for large generator sets, power systems, marine diesel generators, gas turbine generators, and UPS systems.
The system delivers 6,000kW of active power and 4,500kvar of reactive power, with an adjustable power factor ranging from PF 0.8 to 1.0. It provides independent control of the resistive and reactive loads, together with modular forced-air cooling and dual power supplies featuring automatic fast transfer for the cooling fans. Equipped with PLC-based intelligent control, the system incorporates comprehensive protection functions, including temperature, airflow, short-circuit, overvoltage, over- and under-frequency, insulation, and smoke protection. Supporting steady-state, transient, step-load, and automatic testing modes, it can simultaneously acquire, record, and analyze test parameters while generating detailed test reports. This provides a safe, accurate, and traceable solution for large-scale power system performance verification.
Key Features and Advantages
Product Specifications
| Moving load parameters | System Composition | Load cell enclosure, high-voltage switch gear, dry- type transformer , resistive load, inductive load, data acquisition system, control system, cooling system, protection system |
| Active power | 6000 kW | |
| reactive power | 4500kVAR | |
| Apparent power | 7500kVA | |
| Load rated voltage | AC 380V (stepped down to 380V via a transformer ) | |
| Rated frequency | 50Hz | |
| Load characteristics | The resistor and inductor are integrated , and the resistor and reactance can be separated for switching on and off. | |
| Power factor | PF = 0.8~1.0 adjustable | |
| Load connection | Three-phase four- wire | |
| Three-phase balance | Imbalance degree ≤ ±2% | |
| Loading accuracy | ≤±2% | |
| Load step value | 10 kW / 7.5 kVAR | |
| Cooling method | Forced air cooling , with a fan as the core module. | |
| Fan power supply | Automatic fast switching between two power sources (internal and external). | |
| Air intake and exhaust methods | Side air intake, top air exhaust | |
| Load temperature rise | Temperature rise ≤120℃ at 1 meter from air outlet | |
| working methods | Continuous working | |
| Load control power supply | AC 380 V/50Hz | |
| Measurement/display accuracy | ±0.5%FS | |
| Insulation class | F | |
| resistive materials | Special alloy resistor | |
| Load control System parameters |
Control method | Local/Remote |
| Control Mode | Manual/Automatic | |
| Loading function | Individual control loading & joint control loading (capable of parallel operation with AC6.6kV-4200kW-RL and AC6.6kV-3000kVA-RL/AC mobile test loads within the plant) | |
| Measurement and control functions | A, V, Hz, kW, COSΦ acquisition and display | |
| Control response time | ≤200ms | |
| Load protection | Protection mechanisms include short circuit, high temperature, airflow control, and emergency shutdown. | |
| Operating ambient temperature | -20 ℃ to + 50 ℃ | |
| Operating environment humidity | 50% ~ 95% | |
| Load cell operating environment and parameters | Working height | 2000m and below |
| relative humidity | ≤95% No condensation | |
| Atmospheric pressure | 86-106 kPa | |
| Container size | 13000 mm × 2438 mm × 2896 mm (Length × Width × Height) | |
| weight | Each unit has a load capacity of approximately 20 tons. | |
| Protection level | IP5 4 | |
| Location of use | Outdoor (resistant to salt spray, sandstorms, rain, snow, etc.) | |
| Installation and transportation | The box body is equipped with load-bearing lifting holes at its four corners to meet hoisting requirements. | |
| Load scaling | Parallel expansion of 1+N loading containers | |
| Box color | According to customer requirements | |
| Scope of application | Suitable for gas turbine generator sets, marine diesel generator sets, land-based diesel generator sets, and UPS systems. |