Product Introduction
Designed with a 400Vac rated testing voltage and 1kW load step resolution, the RTLBS90L offers granular control over load testing scenarios, while its continuous duty cycle and robust construction (cold rolled stainless steel enclosure, IP54 control chamber) ensure seamless operation in harsh ambient conditions ranging from -20°C to +50°C and at altitudes up to 2000m.a.s.l.
Equipped with advanced Siemens PLC control, patented Nexus-1 software, and support for Mod Bus TCP/RS485 remote communication, it enables automated, real-time testing with data logging and reporting capabilities—streamlining testing workflows for power system manufacturers, maintenance firms, and industrial facilities worldwide. Certified to ISO9001, ISO14001, ISO45001, and CE, this load bank combines cutting-edge technology with eco-friendly design, meeting the stringent ESG and quality requirements of the global electrical testing market.
Structure drawing
Data sheet : 90kw resistive AC load bank
|
Description |
|
|
Model No. |
RTLBS90L |
|
Country of origin |
China |
|
Rated testing voltage |
400Vac |
|
Control voltage (Auxiliary power supply) |
220Vac /230Vac |
|
Frequency |
50Hz. |
|
Phases & Wires |
3P4W |
|
Load step resolution |
1kW |
|
Active load steps (kW) |
1kw+2kw*2+5kw+10kw*2pcs+20kw+40kw |
|
Length*Width*Height(mm) |
104*97.5*121cm |
|
Fans Nos.& Airflow volume |
9* 410CFM/H |
|
Estimated Weight (kg) |
170kgs |
|
Other information |
|
|
Whole machine accuracy |
±3% |
|
Voltage Tolerance (Short Term Operation) |
± 5% |
|
Load Element Tolerance |
≤+2.5% |
|
Load Connections |
Copper terminal |
|
Protection |
Thermal emergency cut out |
|
Air flow switch |
|
|
Fan overload protection |
|
|
Emergency stop |
|
|
Horizontal air forced cooling |
|
|
Airflow direction |
Horizontal air forced cooling |
|
Fan type |
Airfoil axial fan |
|
Load switching contactor type |
AC contactors |
|
Rated maximum/minimum ambient temp. operation |
+50°C / -20°C |
|
Altitude rating |
≤2000 [m.a.s.l] |
|
Control chamber IP rating |
IP 54 outdoor |
|
Enclosure material |
Cold rolled stainless steel plate with painting. |
|
Enclosure color |
RAL 7035 |
|
Portability |
Casters |
|
Certificates |
ISO9001:2015,ISO14001:2015,ISO45001:2018,CE |
|
Duty cycle |
Continuous |
|
Resistor |
|
|
Resistor material |
finned resistor, AISI304/stamped elements |
|
8020 Ni-Cr alloy |
|
|
Stainless steel tube |
filled with magnesium oxide powder |
|
Insulation impedance |
DC1000V 20MΩ above |
|
Insulation Test voltage |
2000 Vac for 1min |
|
Withstand temperature |
About 800℃ |
|
Resistance error |
± 3% |
|
Main parts brands |
|
|
Main parts brands |
Contactor: Schneider or equivalent Relay: CHINT or equivalent |
|
Fuse: Delixi or equivalent |
|
|
Emergency stop: Schneider |
|
|
Load bank control system 1 |
|
|
Manual control |
HMI |
|
Load bank control system 2 |
|
|
PLC control |
Remote PC control with patented software Nexus-1 |
|
Support printing |
Table saved by Excel,curve saved by word. |
|
Remote computer automatic control |
Mod Bus TCP or RS485 communication protocol |
|
Control software in English version(commissioning well before |
|
|
sent to user) |
|
|
Siemens PLC system |
|
|
Function include load data monitor, acquisition, curve, chart, load |
|
|
data save and printing. |
|
|
Quality warranty |
|
|
12 months start from the day receiving the goods at your side. |
|
|
Services |
|
|
7×24 hours service(subject to time zone difference) |
|
|
Online meeting available anytime. |
|
|
Technician guidance online freely, technician going abroad in charged(negotiable). |
|
|
Documents providing |
|
|
Factory report. |
|
|
Operation and maintenance instructions. |
|
|
Structure diagrams & Electrical schematic diagram after deposit. |
|
Main parts