RATA 7500kVA Generator Load Testing with High Power Resistive & Reactive Load Bank

Project Overview

Project Name The 7500kVA Load Bank for Yangjiang Nuclear Power Station Undertaken by RATA Has Successfully Passed the 10h Load Test (RATA On-site Test Project in Guangdong)
Client Name Yangjiang Nuclear Power Station
Project Site China Guangdong
Industry of Application Generator testing
Project Date 2026.08
Test Object  Gas Generator
Test Purpose Carry out an uninterrupted full-power actual load test of more than 10 hours
Supplied Equipment RATA  7500kVA Resistive & Reactive Load Bank

Customer Requirements

Project Background:

● High-reliability Parallel Operation: As the primary equipment, this unit can operate in parallel and serve as mutual hot standby with the existing on-site AC6.6kV-4200kW-RL mobile test load and AC6.6kV-3000kVA-RL/AC mobile test load. It ensures that faulty equipment can be electrically disconnected from the system without shutting down the emergency diesel generators.

The system adopts intelligent fault tolerance and protection design, featuring a fan-centric load linkage mechanism. The failure of a single fan will only cut off its associated load without affecting the operation of other modules. The cooling fans are equipped with dual-power automatic fast transfer function. Temperature monitoring and overheat protection are installed for resistor/reactor units. In the event of overheating, only the faulty load will be disconnected while the fans remain running, and detailed event logs will be recorded.

Comprehensive safety measures are implemented. Short-circuit protection is configured for each power stage of the electrical system, and overcurrent as well as instantaneous overcurrent protection are fitted at the transformer incoming terminal. The equipment has an IP54 protection rating and can operate in rainy conditions. All cables are halogen-free flame-retardant with adequate thermal insulation protection.

Flexible control and data recording are available. Switching between remote control and local control modes is supported, and the load status remains unchanged during switching. The control system is capable of complete operation log recording and test parameter analysis, with a storage capacity of 100M and support for secondary graph plotting.

Strict verification standards are enforced. Before delivery, the equipment will undergo an uninterrupted full-power actual load test lasting more than 10 hours to verify its stability under long-duration operation.

Load Bank Technical Specification

Equipment Model: RATA 8250kVA Resistive & Reactive Load Bank

Main Electrical Parameters
System Composition Load enclosure, high‑voltage switchgear, dry‑type transformer, resistive load, inductive load, acquisition system, control system, cooling system and protection system
Active Power 6000kW
Reactive Power 4500kVAR
Apparent Power 7500kVA
Rated Load Voltage AC380V (stepped‑down to 380V via transformer)
Rated Frequency 50Hz
Load Characteristics Integrated resistive‑inductive load; resistors and reactors can be switched on and off independently
Power Factor PF=0.8~1.0 adjustable
Load Connection Three‑phase four‑wires

Three‑phase Balance

Unbalance degree ≤ ±2%
Loading Accuracy ≤ ±2%
Loading Step Value 10kW / 7.5kVAR
Cooling Method Forced air cooling with fan‑centric modular design
Fan Power Supply Dual‑power supply (internal / external) with automatic fast transfer
Air Inlet & Outlet Mode Side air intake, top air outlet
Load Temperature Rise Temperature rise ≤120℃ at 1‑meter position from air outlet
Operation Mode Continuous‑duty operation
Load Control Power Supply AC380V/50Hz
Measurement & Display Accuracy ±0.5%FS
Insulation Class Class F
Resistor Material Special‑alloy resistors
Load Control‑Control Mode Local / Remote
System Parameters‑Control Mode Manual / Automatic
Loading Function Independent loading & combined loading (supports parallel‑operation with on‑site AC6.6kV‑4200kW‑RL and AC6.6kV‑3000kVA‑RL/AC mobile test loads)
Measurement & Control Function A, V, Hz, kW, cosΦ acquisition and display
Control Response Time ≤200ms
Load Protection Short‑circuit, over‑temperature, abnormal airflow, emergency stop and other protections
Operating Ambient Temperature ‑20℃ ~ +50℃
Operating Ambient Humidity 50% ~ 95%
Operating Altitude 2000 m and below
Relative Humidity ≤95%, non‑condensing
Atmospheric Pressure 86‑106 kPa
Container Dimensions 13000 mm × 2438 mm × 2896 mm (L × W × H)
Weight Approx. 20 tons per unit
Protection Rating IP54
Application Location Outdoor (salt‑spray, dust, rain‑snow resistant)
Installation & Transportation Load‑bearing lifting lugs fitted at four corners of enclosure to satisfy hoisting requirements
Load Expansion Parallel expansion of 1+N load containers
Enclosure Colour Subject to customer requirements
Application Scope Suitable for gas‑turbine generator sets, marine diesel generator sets, land‑based diesel generator sets and UPS systems

Application Scenario

After the completion of manufacturing of the load equipment, the following tests shall be carried out: rated power and load‑capacity test, load‑regulation accuracy test, electrical‑parameter fluctuation test under various working conditions, temperature‑rise test, overload and protection‑function test, insulation test, power‑frequency withstand‑voltage test, enclosure protection‑rating test, earthing test, and continuous full‑load capability test (full‑load operation for no less than 24 hours).

Project Progress

Aug 18, 2026: IRATA technical engineers and production personnel were present at the site.

33da8f77febe2626451f52dc8a1a3517_副本
33da8f77febe2626451f52dc8a1a3517_副本
ec725abec54fad479560f4e21e07cc79_副本
ec725abec54fad479560f4e21e07cc79_副本
1a73b08379d8846e7b09eb954ab5dac2_副本
1a73b08379d8846e7b09eb954ab5dac2_副本
3_副本
3_副本
0 (9)
0 (9)
IMG_5666_副本
IMG_5666_副本
IMG_5697_副本
IMG_5697_副本
4204eda2c241e51f9cfd628286676d37_副本
4204eda2c241e51f9cfd628286676d37_副本

Project Highlights

(1) High-Capacity 7500 kVA Resistive-Inductive Load;

(2) Independent Active and Reactive Load Adjustment;

(3) Designed for 6.6 kV Emergency Generator Testing;

(4) Fan-Centred Modular Fault Isolation;

(5) Dual-Power Automatic Fast Transfer for Cooling Fans;

(6) Forced-Air Cooling and Temperature-Based Protection;

(7) Intelligent Measurement, Control and Test Data Recording;

(8) Parallel Operation with Multiple Load Systems;

(9) Protection for Coastal Salt-Spray Environments.