Project Overview
| Project Name | Weichai Heavy Machinery China State Shipbuilding SIRLC-4000L Resistive-Reactive-Capacitive Load Bank (RATA On-site Test Project in Shandong Weifang) |
| Client Name | Weichai Heavy Machinery |
| Project Site | China Shandong |
| Industry of Application | Marine engines, high‑power complete generator sets |
| Project Date | 2026.08 |
| Test Object | Generator testing |
| Test Purpose | Generator commissioning, performance verification, classification test |
| Supplied Equipment | RATA SIRLC-4000L Resistive & Reactive & Capacitive Load Bank |
Customer Requirements
Project Background: This project procures two sets of 4MW container‑type integrated RLC dry‑type loads, to be deployed at an outdoor test site in Weifang, Shandong Province. To address the limitation of conventional loads that cannot simulate leading reactive‑power operating conditions, the equipment integrates resistive, inductive and capacitive load units and supports multiple high‑voltage and low‑voltage input levels. The two sets can operate in parallel. Equipped with a full suite of test functions including steady‑state test, transient step‑on/step‑off load test, harmonic analysis and waveform recording, the loads can interface with an external test‑bench system for comprehensive performance verification of high‑power generator sets.
Load Bank Technical Specification
Equipment Model: RATA SIRLC-4000L Resistive & Reactive &Capicitive Load Bank
| Main Electrical Parameters | |
| Load Type | Resistive & Reactive& Capicitive Load Bank |
| Rated Capacity | 4000 kW /+3000 kVar+1937.29kVar |
| Power Factor | 0.8 |
| Test Voltage | Low‑voltage: 480 V; High‑voltage: 13.8 kV |
| Frequency | 50Hz / 60Hz |
| Phase | 3 Phase 4 Wire |
| Load Resolution | Resistive‑load resolution: 1 kW; inductive‑load resolution: 1 kVar; capacitive‑load resolution: 1 kVar. Inductive load, capacitive load and resistive load shall all be independently adjustable. |
| Load Accuracy | ≤ ±3% |
Marine Application Scenario
Scientific research, type test and factory acceptance of high‑power diesel/gas generator sets; simulation of actual operating conditions with multiple leading/lagging power factors; performance testing for UPS and power‑supply equipment; support for single‑unit and parallel‑connected load endurance tests. The equipment is of outdoor container‑type construction, capable of withstanding harsh outdoor environments and can be connected to third‑party automated test platforms.
Project Progress
Aug 10, 2026: RATA technical engineers and production personnel were present at the site.
Project Highlights
Integrated RLC resistive‑inductive‑capacitive design with three‑load independent adjustability. It can simulate multiple leading/lagging power‑factor operating conditions to truly restore actual power‑consumption scenarios of generator sets;
Compatible with multiple high‑voltage and low‑voltage levels, supporting 50 Hz / 60 Hz operation. Two units can be operated in parallel for capacity expansion;
High‑speed transient sampling at 40 μs, featuring a full set of test capabilities including steady‑state test, settling test, fluctuation test, transient load‑on / load‑off test, harmonic analysis and waveform recording;
Intelligent software platform with Chinese‑English switchable interfaces. Open communication protocols are provided for interfacing with third‑party automated test benches;
Outdoor‑container‑type structure for easy maintenance. Equipped with comprehensive multi‑layer interlock protections for electrical circuits, temperature and fans;
Adaptable to harsh outdoor environments. Complete factory tests and on‑site handover tests are performed, supported by comprehensive technical documentation and after‑sales service guarantees.